IF Module
Functional - IF Modules (Inter Face)
Fits all Stratos Models - Simple Field Installation Possible
External Min/0 - 10 Vdc/DP 0 - 10 Volt DC External Input - Sets either pump speed or head set point (over rides eletronic control) - Input resistance greater than 100k Ohm, Dielectric strength 24 V, Accuracy +/-5% External Minimum - potential free open terminals (jumper included) - Close circuit normal operation - open contact pump runs at min speed - Max contact load 24 Vdc/10mA, Dielectric strength 250 Vac DP double pump terminals - hook up second (slave) pump
External OFF/0 - 10 VDC/DP 0 - 10 Volt DC External Input - Sets either pump speed or head set point (over rides eletronic control) - Input resistance greater than 100k Ohm, Dielectric strength 24 V, Accuracy +/-5% External Off - potential free normally open input terminals (jmper included) - Closed circuit normal operation - open contact stops power to motor, drive stay active - Pump exercises every 24 hours - no need for additional relays - Max contact load 24 VDC/10mA, Dielectric strength 250 Vac DP double pump terminals - hook up second (slave) pump
LON/DP - LON interface for LonWorks BMS building automations - FTT 10 A - LONTALK - DP double pump termials - hook up second (slave) pump